INPUT / OUTPUT MODULE SPECIFICATIONS

The IO module provides RTD inputs; analog inputs and outputs; and digital inputs and outputs. The IO module will communicate to the Control Module using a serial CANBus interface. Multiple IO modules can be dropped on the CANBus interface to allow IO expansion when required. Identical IO modules will be used for IO expansion.

Environmental:

  • Operating temperature range:      32°F – 122°F       (0 – 50°C) minimum rage
  • Storage temperature range:         -10°F to 140°F    (-23 – 60°C) minimum range
  • Max relative humidity:                   92.5% non-condensing to 2000m altitude
  • Ingress rating:                               NEMA 1 (to be mounted in NEMA12 to 4x enclosure)
  • Power requirement:                       24Vdc to control board;   100 – 240VAC  to be supplied to panel
  • UL / CSA / CE approvals
  • Hazardous area purged panel applications

Module Power Requirements:

Voltage:        24VDC
Power:           50W

IO Module Inputs:

  •  – Analog inputs   (qty 13)
  • 4 – 20ma; 12- bit  resolution; 0.5 % accuracy; channel common reference to controller common
  • – Motor current analog input   (qty 1)
  • Current rating:   0 – 5A ac; Voltage rating:   0 – 30Vac max
  • – On-board analog input for monitoring 24Vdc power supply  (qty 1)
  • – Temperature sensor inputs   (qty 10)
  • 3-wire RTD, 100 ohm PT; 12- bit  resolution; 0.5 % accuracy
  • – Analog outputs   (qty 4)
  • 4-20ma; 10 or 12 bit resolution
  • – Digital inputs  (qty 10)
  • Dry contact; 24Vdc sinking; LED indicator on each channel
  • – Digital outputs (24Vdc)   (qty 11)  
  • Load rating:  1Adc per output, 6Adc max load all digital outputs
  • Isolated / protected; LED indicator on each channel
  • – Emergency stop dry contact  input channel   (qty 1)
  • Failsafe interlocks: with motor output channel & emergency stop input
  • Solid state motor 24Vdc control output
  •  

I/O Expansion Module:

  • Up to 3 IO modules can be attached to the CANBus interface to allow additional IO expansion.
  • Each IO module will have a unique CANBus ID number.