英格索兰Ingersoll Rand /卡麦隆Cameron 离心式空压机 MU I/O模块
2020-07-01
英格索兰Ingersoll Rand 离心式空压机 主控制系统
英格索兰Ingersoll Rand 离心式空压机 控制盘/控制主板,卡麦隆Cameron离心式空压机 MU I/O模块
离心式空压机IO模块,控制板,控制盘 备件号:AAP3798102-00131 / P3798102-00131
INPUT / OUTPUT MODULE SPECIFICATIONS
The IO module provides RTD inputs; analog inputs and outputs; and digital inputs and outputs. The IO module will communicate to the Control Module using a serial CANBus interface. Multiple IO modules can be dropped on the CANBus interface to allow IO expansion when required. Identical IO modules will be used for IO expansion.
Environmental:
- Operating temperature range: 32°F – 122°F (0 – 50°C) minimum rage
- Storage temperature range: -10°F to 140°F (-23 – 60°C) minimum range
- Max relative humidity: 92.5% non-condensing to 2000m altitude
- Ingress rating: NEMA 1 (to be mounted in NEMA12 to 4x enclosure)
- Power requirement: 24Vdc to control board; 100 – 240VAC to be supplied to panel
- UL / CSA / CE approvals
- Hazardous area purged panel applications
Module Power Requirements:
Voltage: 24VDC
Power: 50W
IO Module Inputs:
- – Analog inputs (qty 13)
- 4 – 20ma; 12- bit resolution; 0.5 % accuracy; channel common reference to controller common
- – Motor current analog input (qty 1)
- Current rating: 0 – 5A ac; Voltage rating: 0 – 30Vac max
- – On-board analog input for monitoring 24Vdc power supply (qty 1)
- – Temperature sensor inputs (qty 10)
- 3-wire RTD, 100 ohm PT; 12- bit resolution; 0.5 % accuracy
- – Analog outputs (qty 4)
- 4-20ma; 10 or 12 bit resolution
- – Digital inputs (qty 10)
- Dry contact; 24Vdc sinking; LED indicator on each channel
- – Digital outputs (24Vdc) (qty 11)
- Load rating: 1Adc per output, 6Adc max load all digital outputs
- Isolated / protected; LED indicator on each channel
- – Emergency stop dry contact input channel (qty 1)
- Failsafe interlocks: with motor output channel & emergency stop input
- Solid state motor 24Vdc control output
-
I/O Expansion Module:
- Up to 3 IO modules can be attached to the CANBus interface to allow additional IO expansion.
- Each IO module will have a unique CANBus ID number.