Type | LCON_TA_DFDT |
---|---|
HS code | X756340 |
INPUT TECHNICAL DATA | |
Signal type IN | PT100, PT1000, potentiometer 0…600kΩ, thermocouples (B, C, E, J, K, N, R, S, T) |
Input range IN | -200…+2400°C, based on sensor |
Parametrization IN | DIP switch, FDT/DTM software (1) |
OUTPUT TECHNICAL DATA | |
Signal type OUT | analogue |
Output range OUT | 0…10 V / 0…20 mA / 4…20 mA |
Maximum output signal OUT | 10.5 V (current output) / 21 mA (voltage output) |
Load impedance OUT | >2 kΩ (voltage output) / < 700 Ω (current output) |
Status indication | LED |
Parametrization OUT | DIP switch, FDT/DTM software (1) |
GENERAL TECHNICAL DATA | |
Power supply voltage | 24 Vdc (16.8…30 Vdc) |
Current consumption | 18 mA |
Accuracy | 0.2% FSR (for PT) / 0.4% FSR (for TC) |
Linearity error | ±0.1% FSR |
Temperature coefficient | <100 ppm / K FSR |
Setting time | 5…500 ms (adjustable, default 30 ms) |
Resolution | 16 bit |
Operating temperature range | -40…+70°C |
Insulation | 2.5 kVac / 60 s |
Insulation type | 3-way (IN / OUT / power) |
Overvoltage category / pollution degree | II / 2 |
Protection degree | IP 20 |
Connection terminal IN / OUT | 1.5 mm² / 1.5 mm² (screw) |