Type | LCON_TLS_FDT – |
---|---|
HS code | X756370 |
INPUT TECHNICAL DATA | |
Signal type IN | PT100, PT1000, potentiometer, thermocouples (B, C, E, J, K, N, R, S, T) |
Input range IN | -200…+2400°C (based on sensor) or 0…600 kΩ |
Parametrization IN | software FDT/DTM (1) |
OUTPUT TECHNICAL DATA | |
Signal type OUT | 2 NA contacts (solid state relay) |
Output range OUT | 30 Vdc / 100 mA |
Status indication | LED |
Operating mode OUT | limit value, window, trend, inversion and memory |
Parametrization OUT | FDT/DTM software (1) |
GENERAL TECHNICAL DATA | |
Power supply voltage | 24 Vdc (16.8…30 Vdc) |
Current consumption | 12 mA |
Accuracy | 0.2% FSR / 0.4% FSR |
Linearity error | ±0.1% FSR |
Temperature coefficient | <100 ppm/K |
Setting time | 1…500 ms (adjustable, default 30ms) |
Resolution | 16 bit |
Operating temperature range | -40…+70°C |
Insulation | 2.5 kVac / 60 s |
Insulation type | 2-way (IN-OUT) |
Overvoltage category / pollution degree | II / 2 |
Protection degree | IP 20 |
Connection terminal IN / OUT | 1.5 mm² / 1.5 mm² (screw) |