Type | CWTH6-0844 |
---|---|
Code | X756844 |
INPUT TECHNICAL DATA | |
Signal type IN | thermocouple (J / K) |
Input range IN | 8 programmable ranges (see tab. 1) |
Parametrization IN | DIP switch |
OUTPUT TECHNICAL DATA | |
Signal type OUT | analogue |
Output range OUT | 0…10 V / 0…20 mA / 4…20 mA |
Maximum output signal OUT | 21 mA (voltage input) |
Load impedance OUT | >1 kΩ (voltage output) / < 400 Ω (current output) |
Ripple | <5 mV |
Status indication | LED |
Parametrization OUT | DIP switch |
GENERAL TECHNICAL DATA | |
Power supply voltage | 24 Vac/dc (16.8…30 Vdc / 19.2…28.8 Vac) |
Current consumption | 10 mA |
Accuracy | 0.5% FSR |
Linearity error | 0.1% FSR |
Temperature coefficient | <150 ppm / K FSR |
Transmission frequency | 10 Hz |
Rise time | 30 ms |
Operating temperature range | -25…+60°C |
Insulation | 4 kVac / 60 s |
Insulation type | 3-way (IN / OUT / power) |
Standard approvals | IEC 664-1, DIN VDE |
EMC Standard | EN 50081-2, EN 50082-2 |
Overvoltage category / pollution degree | II / 2 |
Protection degree | IP 20 |
Connection terminal IN / OUT | 2.5 mm² / 2.5 mm² (screw) |