| Type | CSA120BC |
|---|---|
| Code | XCSA120BC |
| INPUT TECHNICAL DATA | |
| Input rated voltage | 12 Vdc |
| Input voltage DC | 10.5…18 Vdc |
| Current consumption | 10 A (12 Vdc) ±10% |
| Inrush peak current | 60 A |
| Internal protection fuse | T 20 A |
| External protection on AC line | MT: C-25 A / Fuse: T-25 A |
| OUTPUT TECHNICAL DATA | |
| Output voltage range | 24 Vdc |
| Output adjustable range | 22.5…27.5 Vdc |
| Continuous current | 5 A (24 Vdc) |
| Overload limiting | 6.5 A |
| Short circuit peak current | 12 A for 300 ms |
| Ripple @ nominal ratings | 100 mVpp |
| Hold up time | 1 ms |
| Status indication | LED “DC OK” |
| Parallel connection | possible |
| Redundant parallel connection | possible with external ORing diode |
| GENERAL TECHNICAL DATA | |
| Efficiency | 83% (12 Vdc) |
| Dissipated power | 25 W (12 Vdc) |
| Operating temperature range | –20…+50°C |
| Input / output isolation | 2.1 kVdc / 60s |
| Input / ground isolation | 1.41 kVdc / 60s |
| Output / ground isolation | 0.75 kVdc / 60s |
| Standard / approvals | EN 60950-1 |
| EMC Standard | EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4 |
| Overvoltage category / pollution degree | II / 2 |
| Protection degree | IP 20 |
| Connection terminal | 2.5 mm² / 2.5 mm² |