Cabur XCSA120BC 电源

2025-06-25

Type CSA120BC
Code XCSA120BC
INPUT TECHNICAL DATA  
Input rated voltage 12 Vdc
Input voltage DC 10.5…18 Vdc
Current consumption 10 A (12 Vdc) ±10%
Inrush peak current 60 A
Internal protection fuse T 20 A
External protection on AC line MT: C-25 A / Fuse: T-25 A
OUTPUT TECHNICAL DATA  
Output voltage range 24 Vdc
Output adjustable range 22.5…27.5 Vdc
Continuous current 5 A (24 Vdc)
Overload limiting 6.5 A
Short circuit peak current 12 A for 300 ms
Ripple @ nominal ratings 100 mVpp
Hold up time 1 ms
Status indication LED “DC OK”
Parallel connection possible
Redundant parallel connection possible with external ORing diode
GENERAL TECHNICAL DATA  
Efficiency 83% (12 Vdc)
Dissipated power 25 W (12 Vdc)
Operating temperature range –20…+50°C
Input / output isolation 2.1 kVdc / 60s
Input / ground isolation 1.41 kVdc / 60s
Output / ground isolation 0.75 kVdc / 60s
Standard / approvals EN 60950-1
EMC Standard EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4
Overvoltage category / pollution degree II / 2
Protection degree IP 20
Connection terminal 2.5 mm² / 2.5 mm²