| Type | CSA120DC |
|---|---|
| Code | XCSA120DC |
| INPUT TECHNICAL DATA | |
| Input rated voltage | 48 Vdc |
| Input voltage DC | 36…72 Vdc |
| Current consumption | 2.8 A (48 Vdc) ±10% |
| Inrush peak current | 120 A |
| Internal protection fuse | T 5 A |
| External protection on AC line | MT: C-6 A / Fuse: T-6 A |
| OUTPUT TECHNICAL DATA | |
| Output voltage range | 24 Vdc |
| Output adjustable range | 22.5…27.5 Vdc |
| Continuous current | 5A (24 Vdc) |
| Overload limiting | 6.5 A |
| Short circuit peak current | 13 A for 300 ms |
| Ripple @ nominal ratings | 200 mVpp |
| Hold up time | 4.5 ms |
| Status indication | LED “DC OK” |
| Parallel connection | possible |
| Redundant parallel connection | possible with external ORing diode |
| GENERAL TECHNICAL DATA | |
| Efficiency | 90% (48 Vdc) |
| Dissipated power | 13 W (48 Vdc) |
| Operating temperature range | –20…+50°C |
| Input / output isolation | 2.1 kVdc / 60s |
| Input / ground isolation | 1.41 kVdc / 60s |
| Output / ground isolation | 0.75 kVdc / 60s |