| Type | CSA240FC |
|---|---|
| Code | XCSA240FC |
| INPUT TECHNICAL DATA | |
| Input rated voltage | 110 Vdc |
| Input voltage DC | 100…130 Vdc |
| Current consumption | 2.4 A (110 Vdc) ±10% |
| Inrush peak current | 150 A |
| Internal protection fuse | T 5 A |
| External protection on AC line | MT: C-6 A / Fuse: T-6 A |
| OUTPUT TECHNICAL DATA | |
| Output voltage range | 24 Vdc |
| Output adjustable range | 23…27 Vdc |
| Continuous current | 10 A at 50°C |
| Overload limiting | 15 A |
| Short circuit peak current | 21 A for 300 ms |
| Ripple @ nominal ratings | 100 mVpp |
| Hold up time | 4 ms |
| Status indication | LED “DC OK” |
| Alarm contact | dry contact, max. 1A @ 24 Vdc |
| Parallel connection | possible |
| Redundant parallel connection | already fitted with internal ORing diode |
| GENERAL TECHNICAL DATA | |
| Efficiency | 89% (110 Vdc) |
| Dissipated power | 28W (110 Vdc) |
| Operating temperature range | –20…+60°C (derating -6 W >50°C) |
| Input / output isolation | 2.1 kVdc / 60s |
| Input / ground isolation | 1.41 kVdc / 60s |
| Output / ground isolation | 0.75 kVdc / 60s |