Type | CSA240FC |
---|---|
Code | XCSA240FC |
INPUT TECHNICAL DATA | |
Input rated voltage | 110 Vdc |
Input voltage DC | 100…130 Vdc |
Current consumption | 2.4 A (110 Vdc) ±10% |
Inrush peak current | 150 A |
Internal protection fuse | T 5 A |
External protection on AC line | MT: C-6 A / Fuse: T-6 A |
OUTPUT TECHNICAL DATA | |
Output voltage range | 24 Vdc |
Output adjustable range | 23…27 Vdc |
Continuous current | 10 A at 50°C |
Overload limiting | 15 A |
Short circuit peak current | 21 A for 300 ms |
Ripple @ nominal ratings | 100 mVpp |
Hold up time | 4 ms |
Status indication | LED “DC OK” |
Alarm contact | dry contact, max. 1A @ 24 Vdc |
Parallel connection | possible |
Redundant parallel connection | already fitted with internal ORing diode |
GENERAL TECHNICAL DATA | |
Efficiency | 89% (110 Vdc) |
Dissipated power | 28W (110 Vdc) |
Operating temperature range | –20…+60°C (derating -6 W >50°C) |
Input / output isolation | 2.1 kVdc / 60s |
Input / ground isolation | 1.41 kVdc / 60s |
Output / ground isolation | 0.75 kVdc / 60s |