Type | CSF120C |
---|---|
Code | XCSF120C |
INPUT TECHNICAL DATA | |
Input rated voltage | 120–230 Vac |
Input voltage AC | 90…264 Vac |
Input voltage DC | 100…345 Vdc (derating Uin |
Frequency | 47…63 Hz |
Current consumption | 1.9 A (120 Vac) / 1.1 A (230 Vac) |
Inrush peak current | 20 A |
Power factor | > 0.65 |
Internal protection fuse | T 3.15 A |
External protection on AC line | MT: C-4 A / Fuse: T 4 A |
OUTPUT TECHNICAL DATA | |
Output voltage range | 24 Vdc |
Output adjustable range | 23…27.5 Vdc |
Continuous current | 5 A at 45°C |
Overload limiting | 8 A for >30 s |
Short circuit peak current | 15 A for 50 ms |
Ripple @ nominal ratings | 30 mVpp |
Hold up time | 17 ms (120 Vac) / 72 ms (230 Vac) |
Status indication | LED “DC OK” / LED “Alarm” |
Alarm contact | dry contact, max. 1A @ 24 Vdc (Uout >21.6 Vdc) |
Parallel connection | possible |
Redundant parallel connection | possible with external ORing diode |
GENERAL TECHNICAL DATA | |
Efficiency | 86% (120 Vac) / 90% (230 Vac) |
Dissipated power | 19 W (120 Vac) / 13 W (230 Vac) |
Operating temperature range | –20…+60°C (derating -1.9 W >45°C) |
Input / output isolation | 3 KVac / 60 s (SELV output) |
Input / ground isolation | 1.5 kVac / 60 s |
Output / ground isolation | 0.5 kVac / 60 s |