| Type | CSF120CP |
|---|---|
| Code | XCSF120CP |
| INPUT TECHNICAL DATA | |
| Input rated voltage | 120–230 Vac |
| Input voltage AC | 90…264 Vac |
| Input voltage DC | 100…345 Vdc (derating Uin |
| Frequency | 47…63 Hz |
| Current consumption | 1.9 A (120 Vac) / 1.1 A (230 Vac) |
| Inrush peak current | 20 A |
| Power factor | > 0.65 |
| Internal protection fuse | T 3.15 A |
| External protection on AC line | MT: C-4 A / Fuse: T 4 A |
| OUTPUT TECHNICAL DATA | |
| Output voltage range | 24 Vdc |
| Output adjustable range | 23…27.5 Vdc |
| Continuous current | 5 A at 45°C |
| Overload limiting | 8 A for >30 s |
| Short circuit peak current | 15 A for 50 ms |
| Ripple @ nominal ratings | 30 mVpp |
| Hold up time | 17 ms (120 Vac) / 72 ms (230 Vac) |
| Status indication | LED “DC OK” / LED “Alarm” |
| Alarm contact | dry contact, max. 1A @ 24 Vdc (Uout >21.6 Vdc) |
