| Type | CSF500D |
|---|---|
| Code | XCSF500D |
| INPUT TECHNICAL DATA | |
| Input rated voltage | 120–230 Vac |
| Input voltage AC | 90…132 Vac / 185…264 Vac (1) |
| Input voltage DC | 259…370 Vdc |
| Frequency | 47…63 Hz |
| Current consumption | 8.4 A (120Vac) / 4.4 A (230Vac) |
| Inrush peak current | 25 A |
| Power factor | > 0.75 |
| External protection on AC line | MT: C-16 A / Fuse: T 15 A |
| OUTPUT TECHNICAL DATA | |
| Output voltage range | 48 Vdc ±1% |
| Output adjustable range | 45…55 Vdc |
| Continuous current | 10 A at 45°C |
| Overload limiting | 12 Af for >5 s |
| Short circuit peak current | 20 A for 5 s |
| Ripple @ nominal ratings | 50 mVpp |
| Hold up time | 12 ms (120 Vac) / 20 ms (230 Vac) |
| Status indication | LED “DC OK” / LED “Alarm” |
| Alarm contact | dry contact, max. 1A @ 24 Vdc (Uout >43.2 Vdc) |
| Parallel connection | possible |
| Redundant parallel connection | already fitted with internal ORing diode |
| GENERAL TECHNICAL DATA | |
| Efficiency | 92% (120 Vac) / 92% (230 Vac) |
| Dissipated power | 44 W (120 Vac) / 44 W (230 Vac) |
| Operating temperature range | –20…+60°C (derating -8.2 W >45°C) |
| Input / output isolation | 3 KVac / 60 s (SELV output) |
| Input / ground isolation | 1.5 kVac / 60 s |
| Output / ground isolation | 0.5 kVac / 60 s |