| Type | CSG2401C |
|---|---|
| Code | XCSG2401C |
| INPUT TECHNICAL DATA | |
| Input rated voltage | 3x 400–500 Vac |
| Input voltage AC | 340…550 Vac |
| Frequency | 47…63 Hz |
| Current consumption | 4.5 A (400 Vac) / 3.5 A (500 Vac) |
| Inrush peak current | 10 A (with active limitation circuit) |
| Power factor | > 0.92 |
| External protection on AC line | MT: C-10 A / Fuse: T 10 A |
| OUTPUT TECHNICAL DATA | |
| Output voltage range | 12-24 Vdc ±1% |
| Output adjustable range | 11.5…29 Vdc |
| Continuous current | 100 A a 45°C |
| Overload limiting | 150 A for >5 s |
| Short circuit peak current | 150 A for 5 s |
| Ripple @ nominal ratings | 200 mVpp |
| Hold up time | 10 ms (400 Vac) / 10 ms (500 Vac) |
| Status indication | LED “DC OK” / LED “Alarm” / Display |
| Alarm contact | dry contact, max. 1A @ 24 Vdc (programmable) |
| Parallel connection | possible |
| Redundant parallel connection | already fitted with internal ORing diode |
| GENERAL TECHNICAL DATA | |
| Efficiency | 92% (400 Vac) / 92% (500 Vac) |
| Dissipated power | 200 W (400 Vac) / 200 W (500 Vac) |
| Operating temperature range | –20…+60°C (derating -40 W >45°C) |
| Input / output isolation | 3 KVac / 60 s (SELV output) |
| Input / ground isolation | 1.5 kVac / 60 s |
| Output / ground isolation | 0.5 kVac / 60 s |
| Standard / approvals | EN 60950-1 |