Type | CSG2401D |
---|---|
Code | XCSG2401D |
INPUT TECHNICAL DATA | |
Input rated voltage | 3x 400–500 Vac |
Input voltage AC | 340…550 Vac |
Frequency | 47…63 Hz |
Current consumption | 4.5 A (400 Vac) / 3.5 A (500 Vac) |
Inrush peak current | 10 A (with active limitation circuit) |
Power factor | > 0.92 |
External protection on AC line | MT: C-10 A / Fuse: T 10 A |
OUTPUT TECHNICAL DATA | |
Output voltage range | 24-48 Vdc ±1% |
Output adjustable range | 23…56 Vdc |
Continuous current | 50 A a 45°C |
Overload limiting | 75 A for >5 s |
Short circuit peak current | 75 A for 5 s |
Ripple @ nominal ratings | 200 mVpp |
Hold up time | 10 ms (400 Vac) / 10 ms (500 Vac) |
Status indication | LED “DC OK” / LED “Alarm” / Display |
Alarm contact | dry contact, max. 1A @ 24 Vdc (programmable) |
Parallel connection | possible |
Redundant parallel connection | already fitted with internal ORing diode |
GENERAL TECHNICAL DATA | |
Efficiency | 93% (400 Vac) / 93% (500 Vac) |
Dissipated power | 180 W (400 Vac) / 180 W (500 Vac) |
Operating temperature range | –20…+60°C (derating -40 W >45°C) |
Input / output isolation | 3 KVac / 60 s (SELV output) |
Input / ground isolation | 1.5 kVac / 60 s |
Output / ground isolation | 0.5 kVac / 60 s |