| Type | CSG960D |
|---|---|
| Code | XCSG960D |
| INPUT TECHNICAL DATA | |
| Input rated voltage | 3x 400–500 Vac |
| Input voltage AC | 340…550 Vac |
| Frequency | 47…63 Hz |
| Current consumption | 2.2 A (400 Vac) / 1.1 A (500 Vac) |
| Inrush peak current | 20 A |
| Power factor | > 0.65 |
| External protection on AC line | MT: C-10 A / Fuse: T 10 A |
| OUTPUT TECHNICAL DATA | |
| Output voltage range | 48 Vdc ±1% |
| Output adjustable range | 45…55 Vdc |
| Continuous current | 20 A at 50°C |
| Overload limiting | 23 A for >5 s |
| Short circuit peak current | 40 A for 5 s |
| Ripple @ nominal ratings | 100 mVpp |
| Hold up time | 10 ms (400 Vac) / 15 ms (500 Vac) |
| Status indication | LED “DC OK” / LED “Alarm” |
| Alarm contact | dry contact, max. 1A @ 24 Vdc (Uout >43.2 Vdc) |
| Parallel connection | possible |
| Redundant parallel connection | already fitted with internal ORing diode |
| GENERAL TECHNICAL DATA | |
| Efficiency | 92% (400 Vac) / 92% (500 Vac) |
| Dissipated power | 80 W (400 Vac) / 80 W (500 Vac) |
| Operating temperature range | –20…+60°C (derating -18 W >45°C) |
| Input / output isolation | 3 KVac / 60 s (SELV output) |
| Input / ground isolation | 2 kVac / 60 s |
| Output / ground isolation | 0.5 kVac / 60 s |
| Standard / approvals | EN 60950-1 |