Type | CSG960G |
---|---|
Code | XCSG960G |
INPUT TECHNICAL DATA | |
Input rated voltage | 3x 400–500 Vac |
Input voltage AC | 340…550 Vac |
Frequency | 47…63 Hz |
Current consumption | 2.2 A (400 Vac) / 1.1 A (500 Vac) |
Inrush peak current | 20 A |
Power factor | > 0.65 |
External protection on AC line | MT: C-10 A / Fuse: T 10 A |
OUTPUT TECHNICAL DATA | |
Output voltage range | 72 Vdc ±1% |
Output adjustable range | 72…85 Vdc |
Continuous current | 13.3 A at 50°C |
Overload limiting | 17 A for >5 s |
Short circuit peak current | 27 A for 5 s |
Ripple @ nominal ratings | 100 mVpp |
Hold up time | 15 ms (400 Vac) / 18 ms (500 Vac) |
Status indication | LED “DC OK” / LED “Alarm” |
Alarm contact | dry contact, max. 1A @ 24 Vdc (Uout >68.4 Vdc) |
Parallel connection | possible |
Redundant parallel connection | already fitted with internal ORing diode |
GENERAL TECHNICAL DATA | |
Efficiency | 94% (400 Vac) / 94% (500 Vac) |
Dissipated power | 60 W (400 Vac) / 60 W (500 Vac) |
Operating temperature range | –20…+60°C (derating -18 W >45°C) |
Input / output isolation | 3 KVac / 60 s (no SELV output) |
Input / ground isolation | 2 kVac / 60 s |
Output / ground isolation | 0.5 kVac / 60 s |