| Type | CSL1-072W/024V/AA |
|---|---|
| Code | XCSL1072W024VAA |
| INPUT TECHNICAL DATA | |
| Input rated voltage | 120–230 Vac |
| Input voltage AC | 85…264 Vac |
| Input voltage DC | 100…370 Vdc (derating Uin |
| Frequency | 47…63 Hz |
| Current consumption | 0.8 A (120 Vac) / 0.4 A (230 Vac) |
| Inrush peak current | 20 A |
| Power factor | > 0.65 |
| Internal protection fuse | T 2 A |
| External protection on AC line | MT: C-4 A / Fuse: T 4 A |
| OUTPUT TECHNICAL DATA | |
| Output voltage range | 24 Vdc |
| Output adjustable range | 16 … 28 Vdc |
| Continuous current | 3 A at 50°C |
| Overload limiting | 6 A for >30 s |
| Short circuit peak current | 15 A for 50 ms |
| Ripple @ nominal ratings | 40 mVpp |
| Hold up time | 20 ms (120 Vac) / 70 ms (230 Vac) |
| Status indication | LED “DC OK” |
| Alarm contact | dry contact, max. 1A @ 24 Vdc (Uout >22.0 Vdc) |
| Parallel connection | possible |
| Redundant parallel connection | possible with external ORing diode |
| GENERAL TECHNICAL DATA | |
| Efficiency | 87% (120 Vac) / 87% (230 Vac) |
| Dissipated power | 10.8 W (120 Vac) / 10.8 W (230 Vac) |
| Operating temperature range | –20…+70°C (derating -3 W/°C >50°C) |
| Input / output isolation | 3 KVac / 60 s (SELV output) |
| Input / ground isolation | 1.5 kVac / 60 s |
| Output / ground isolation | 0.5 kVac / 60 s |