Type | CSL3-480W/024V/AA |
---|---|
HS code | XCSL3480W024VAA |
INPUT TECHNICAL DATA | |
Input rated voltage | 3x 400–500 Vac |
Input voltage AC | 340…550 Vac |
Input voltage DC | 500 – 600 Vdc |
Frequency | 47…63 Hz |
Current consumption | 0.8 A (400 Vac) |
Inrush peak current | 22 A |
Power factor | 0.76 |
External protection on AC line | MT: C-4 A / Fuse: T-3.15 A |
OUTPUT TECHNICAL DATA | |
Output voltage range | 24 Vdc |
Output adjustable range | 20…28.5 Vdc |
Continuous current | 20 A at 50°C |
Overload limiting | 23 A (max. 25 A constant current) |
Short circuit peak current | 35A 400 ms On /800 ms Off (HICCUP mode) |
Ripple @ nominal ratings | 200 mVpp |
Hold up time | 10 ms (400 Vac) |
Status indication | LED “DC OK”, LED “Stand-by” |
Alarm contact | dry contact, max. 1A @ 24 Vdc (Uout >16 Vdc) |
Parallel connection | possible |
Redundant parallel connection | possible with external ORing diode |
GENERAL TECHNICAL DATA | |
Efficiency | 90.5% (400 Vac) |
Dissipated power | 48 W |
Operating temperature range | –20…+70°C (derating -14 W/°C >50°C) |
Input / output isolation | 3 KVac / 60 s (SELV output) |
Input / ground isolation | 1.5 kVac / 60 s |
Output / ground isolation | 0.5 kVac / 60 s |