| Series | Easy Power |
|---|---|
| Code | XCSL3480W048VAB |
| Type | CSL3-480W/048V/AB |
| INPUT TECHNICAL DATA | |
| Input rated voltage | 3x 400–500 Vac |
| Input voltage AC | 340…550 Vac |
| Input voltage DC | 500 – 600 Vdc |
| Frequency | 47…63 Hz |
| Current consumption | 0.8 A (400 Vac) |
| Inrush peak current | 22 A |
| Power factor | 0.76 |
| External protection on AC line | MT: C-4 A / Fuse: T-3.15 A |
| OUTPUT TECHNICAL DATA | |
| Output voltage range | 48 Vdc ±1% |
| Output adjustable range | 40.5 … 55.5 Vdc |
| Continuous current | 10 A at 50°C |
| Overload limiting | 15 A (max. 26 A constant current) |
| Short circuit peak current | 40 A 400 ms On /800 ms Off (HICCUP mode) |
| Ripple @ nominal ratings | 200 mVpp |
| Hold up time | 10 ms (400 Vac) |
| Status indication | LED “DC OK”, LED “Stand-by” |
| Alarm contact | dry contact, max. 1A @ 24 Vdc (Uout >26 Vdc) |
| Parallel connection | possible |
| Redundant parallel connection | possible with external ORing diode |
| GENERAL TECHNICAL DATA | |
| Efficiency | 91% (400 Vac) |
| Dissipated power | 47.5 W (400 Vac) |
| Operating temperature range | –20…+70°C (derating -14 W/°C >50°C) |
| Input / output isolation | 3 KVac / 60 s (SELV output) |
| Input / ground isolation | 1.5 kVac / 60 s |
| Output / ground isolation | 0.5 kVac / 60 s |
| Standard / approvals | EN 60950-1 |
| EMC Standard | EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4 |
| Overvoltage category / pollution degree | II / 2 |
| Protection degree | IP 20 |
| Connection terminal | 4 mm² / 4 mm² |
| Housing material | aluminium |
| Dimensions (LxHxD) | 80x170x127 mm |
| Approximate weight | 1.5 kg |
| Mounting information | vertical on a rail, 20 mm from adjacent components |
| ACCESSORIES | |
| Mounting rail (IEC60715/TH35-7.5) | PR/3/AC, PR/3/AC/ZB, PR/3/AS, PR/3/AS/ZB |