Series | Easy Power |
---|---|
Code | XCSL3480W072VAB |
Type | CSL3-480W/072V/AB (3) |
INPUT TECHNICAL DATA | |
Input rated voltage | 3x 400–500 Vac |
Input voltage AC | 340…550 Vac |
Input voltage DC | 500 – 600 Vdc |
Frequency | 47…63 Hz |
Current consumption | 0.8 A (400 Vac) |
Inrush peak current | 22 A |
Power factor | 0.76 |
External protection on AC line | MT: C-4 A / Fuse: T-3.15 A |
OUTPUT TECHNICAL DATA | |
Output voltage range | 72 Vdc ±1% |
Output adjustable range | 60…81 Vdc |
Continuous current | 6.6 A at 50°C |
Overload limiting | 11 A (max. 22.5 A constant current) |
Short circuit peak current | 20 A 400 ms On /800 ms Off (HICCUP mode) |
Ripple @ nominal ratings | 200 mVpp |
Hold up time | 10 ms (400 Vac) |
Status indication | LED “DC OK”, LED “Stand-by” |
Alarm contact | 68.4 Vdc) |
Parallel connection | possible |
Redundant parallel connection | possible with external ORing diode |
GENERAL TECHNICAL DATA | |
Efficiency | 91.5% (400 Vac) |
Dissipated power | 44.6 W (400 Vac) |
Operating temperature range | –20…+70°C (derating -14 W/°C >50°C) |
Input / output isolation | 3 KVac / 60 s (no SELV output) |
Input / ground isolation | 1.5 kVac / 60 s |
Output / ground isolation | 0.5 kVac / 60 s |
Standard / approvals | EN 60950-1 |
EMC Standard | EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4 |
Overvoltage category / pollution degree | II / 2 |
Protection degree | IP 20 |
Connection terminal | 4 mm² / 4 mm² |
Housing material | aluminium |
Dimensions (LxHxD) | 80x170x127 mm |
Approximate weight | 1.5 kg |