Type | CSL481C |
---|---|
Code | XCSL481C |
INPUT TECHNICAL DATA | |
Input rated voltage | 230 Vac |
Input voltage AC | 187…264 Vac |
Frequency | 47…63 Hz |
Current consumption | 2 A (230 Vac) |
Inrush peak current | 20 A |
Power factor | > 0.95 |
External protection on AC line | MT: C-6 A / Fuse: T-6.3 A |
OUTPUT TECHNICAL DATA | |
Output voltage range | 24 Vdc ±1% |
Output adjustable range | 23…27.5 Vdc |
Continuous current | 20 A at 45°C |
Overload limiting | 28 A |
Short circuit peak current | 50 A for 0.3 s |
Ripple @ nominal ratings | 100 mVpp |
Hold up time | 20 ms (230 Vac) |
Status indication | LED “DC OK” |
Alarm contact | dry contact, max. 1A @ 24 Vdc (Uout >21.6 Vdc) |
Parallel connection | possible |
Redundant parallel connection | possible with external ORing diode |
GENERAL TECHNICAL DATA | |
Efficiency | 92% (230 Vac) |
Dissipated power | 42 W (230 Vac) |
Operating temperature range | –20…+60°C (derating -16 W >45°C) |
Input / output isolation | 3 KVac / 60 s (SELV output) |
Input / ground isolation | 1.5 kVac / 60 s |
Output / ground isolation | 0.5 kVac / 60 s |