Type | CSW241B |
---|---|
Code | XCSW241B |
INPUT TECHNICAL DATA | |
Input rated voltage | 1-2-3x 230-400-500 Vac |
Input voltage AC | 185…550 Vac |
Input voltage DC | 270…725 Vdc |
Frequency | 47…63 Hz |
Current consumption | 2 A (230 Vac) / 1 A (400 Vac) |
Inrush peak current | 20 A |
Power factor | > 0.65 |
External protection on AC line | MT: C-6 A / Fuse: T-6.3 A |
OUTPUT TECHNICAL DATA | |
Output voltage range | 12 Vdc ±1% |
Output adjustable range | 12…15 Vdc |
Continuous current | 16 A (12 Vdc) – 15 A (15 Vdc) |
Overload limiting | 20…18 A for >6 s |
Short circuit peak current | 34 A for 0.5 s |
Ripple @ nominal ratings | 100 mVpp |
Hold up time | 15 ms (230 Vac) / 100 ms (400 Vac) |
Status indication | LED “DC OK” / LED “Alarm” |
Alarm contact | dry contact, max. 1A @ 24 Vdc (Uout >10.8 Vdc) |
Parallel connection | possible |
Redundant parallel connection | possible with external ORing diode |
GENERAL TECHNICAL DATA | |
Efficiency | 89% (230 Vac) / 90% (400 Vac) |
Dissipated power | 22 W (230 Vac) / 20 W (400 Vac) |
Operating temperature range | –20…+60°C (derating -3 W >50°C) |
Input / output isolation | 3 KVac / 60 s (SELV output) |
Input / ground isolation | 2 kVac / 60 s |
Output / ground isolation | 0.5 kVac / 60 s |