| Type | CSW481D |
|---|---|
| Code | XCSW481D |
| INPUT TECHNICAL DATA | |
| Input rated voltage | 1-2-3x 230-400-500 Vac |
| Input voltage AC | 187…550 Vac |
| Input voltage DC | 250…725 Vdc |
| Frequency | 47…63 Hz |
| Current consumption | 2.2 A (230 Vac) / 1 A (400 Vac) |
| Inrush peak current | 20 A (230 Vac) / 40 A (500 Vac) |
| Power factor | > 0.95 |
| External protection on AC line | MT: C-6 A / Fuse: T-6.3 A |
| OUTPUT TECHNICAL DATA | |
| Output voltage range | 48 Vdc ±1% |
| Output adjustable range | 45…55 Vdc |
| Continuous current | 10 A at 45°C |
| Overload limiting | 14 A for >5 s |
| Short circuit peak current | 25 A for 0.3 s |
| Ripple @ nominal ratings | 100 mVpp |
| Hold up time | 20 ms (230 Vac) / 20 ms (400 Vac) |
| Status indication | LED “DC OK” / LED “Alarm” |
| Alarm contact | dry contact, max. 1A @ 24 Vdc (Uout >43.2 Vdc) |
| Parallel connection | possible |
| Redundant parallel connection | possible with external ORing diode |
| GENERAL TECHNICAL DATA | |
| Efficiency | 92% (230 Vac) / 92% (400 Vac) |
| Dissipated power | 42 W (230 Vac) / 42 W (400 Vac) |
| Operating temperature range | –20…+60°C (derating -16 W >45°C) |
| Input / output isolation | 3 KVac / 60 s (SELV output) |
| Input / ground isolation | 2 kVac / 60 s |
| Output / ground isolation | 0.5 kVac / 60 s |
| Standard / approvals | EN 60950-1 |