Type | CSW481G |
---|---|
Code | XCSW481G |
INPUT TECHNICAL DATA | |
Input rated voltage | 1-2-3x 230-400-500 Vac |
Input voltage AC | 187…550 Vac |
Input voltage DC | 250…725 Vdc |
Frequency | 47…63 Hz |
Current consumption | 2.2 A (230 Vac) / 1 A (400 Vac) |
Inrush peak current | 20 A (230 Vac) / 40 A (500 Vac) |
Power factor | > 0.95 |
External protection on AC line | MT: C-6 A / Fuse: T-6.3 A |
OUTPUT TECHNICAL DATA | |
Output voltage range | 72 Vdc ±1% |
Output adjustable range | 72…85 Vdc |
Continuous current | 6 A at 45°C |
Overload limiting | 9 A for >5 s |
Short circuit peak current | 12 A for 0.3 s |
Ripple @ nominal ratings | 100 mVpp |
Hold up time | 20 ms (230 Vac) / 20 ms (400 Vac) |
Status indication | LED “DC OK” / LED “Alarm” |
Alarm contact | dry contact, max. 1A @ 24 Vdc (Uout >68.4 Vdc) |
Parallel connection | possible |
Redundant parallel connection | possible with external ORing diode |
GENERAL TECHNICAL DATA | |
Efficiency | 91% (230 Vac) / 91% (400 Vac) |
Dissipated power | 42 W (230 Vac) / 42 W (400 Vac) |
Operating temperature range | –20…+60°C (derating -16 W >45°C) |
Input / output isolation | 3 KVac / 60 s (no SELV output) |
Input / ground isolation | 2 kVac / 60 s |
Output / ground isolation | 0.5 kVac / 60 s |