Type | CSW960CP |
---|---|
Code | XCSW960CP |
INPUT TECHNICAL DATA | |
Input rated voltage | 1x 230 Vac / 2x 400-500 Vac |
Input voltage AC | 180…264 Vac / 360…550 Vac |
Input voltage DC | 550…775 Vdc |
Frequency | 47…63 Hz |
Current consumption | 4.7A (230 Vac) / 4A A (400 Vac) |
Inrush peak current | 16 A |
Power factor | > 0.6 |
External protection on AC line | MT: C-10 A / Fuse: 1-2x T 10 A |
OUTPUT TECHNICAL DATA | |
Output voltage range | 24 Vdc ±1% |
Output adjustable range | 23…27.5 Vdc |
Continuous current | 40 A a 45°C |
Overload limiting | 50 A for >5 s |
Short circuit peak current | 65 A for 5 s |
Ripple @ nominal ratings | 200 mVpp |
Hold up time | 20 ms (230 Vac) / 20 ms (400 Vac) |
Status indication | LED “DC OK” / LED “Alarm” |
Alarm contact | dry contact, max. 1A @ 24 Vdc (Uout >21.6 Vdc) |
Parallel connection | possible |
Redundant parallel connection | already fitted with internal ORing diode |
GENERAL TECHNICAL DATA | |
Efficiency | 90% (400 Vac) at 230 Vac |
Dissipated power | <100 W (400 Vac) at 230 Vac |
Operating temperature range | –20…+60°C (derating -32 W >45°C) |
Input / output isolation | 3 KVac / 60 s (SELV output) |
Input / ground isolation | 2 kVac / 60 s |
Output / ground isolation | 0.5 kVac / 60 s |
Standard / approvals | EN 60950-1 |
EMC Standard | EN 61000-6-2, EN 61000-6-4 |
Overvoltage category / pollution degree | II / 2 |
Protection degree | IP 20 |