PR Electronics 2-wire HART transmitter PR 6337A

2026-03-31

PR6337A Two-wire HART transmitter

Common specifications

Supply

Supply voltage 8.0…35 VDC
Internal power dissipation, 1 / 2 ch. 19 mW…0.8 / 1.6 W

Isolation voltage

Isolation voltage, test / working 1.5 kVAC / 50 VAC

Response time

Response time (programmable) 1…60 s
Voltage drop 8.0 VDC
Signal dynamics, input 22 bit
Signal dynamics, output 16 bit
Signal / noise ratio > 60 dB
Accuracy Better than 0.05% of selected range
EMC immunity influence < ±0.1% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span

Input specifications

Common input specifications

Max. offset 50% of selected max. value

RTD input

RTD type Pt50/100/200/500/1000; Ni50/100/120/1000
Cable resistance per wire 5 Ω (up to 50 Ω per wire is possible with reduced measurement accuracy)
Sensor current Nom. 0.2 mA

Linear resistance input

Linear resistance min….max. 0 Ω…7000 Ω

TC input

Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5
Cold junction compensation (CJC) Constant, internal or external via a Pt100 or Ni100 sensor

Voltage input

Measurement range -800…+800 mV
Min. measurement range (span) 2.5 mV
Input resistance 10 MΩ

Output specifications

Current output

Signal range 4…20 mA
Min. signal range 16 mA
Load (@ current output) ≤ (Vsupply – 8) / 0.023 [Ω]
Sensor error indication Programmable 3.5…23 mA
NAMUR NE43 Upscale/Downscale 23 mA / 3.5 mA