PR Electronics 2-wire programmable transmitter RTD transmitter PR 5332A
2026-03-20
PR5332A Two-wire programmable transmitter RTD transmitter
Environmental Conditions
| Operating temperature |
-40°C to +85°C |
| Calibration temperature |
20…28°C |
| Relative humidity |
< 95% RH (non-cond.) |
| Protection degree (encl./terminal) |
IP68 / IP00 |
Mechanical specifications
| Dimensions |
Ø 44 x 20.2 mm |
| Weight approx. |
50 g |
| Wire size |
1 x 1.5 mm2 stranded wire |
| Screw terminal torque |
0.4 Nm |
Common specifications
| Supply voltage |
7.2…35 VDC |
| Internal power dissipation |
25 mW…0.8 W |
| Response time (programmable) |
1…60 s |
| Voltage drop |
7.2 VDC |
| Warm-up time |
5 min. |
| Power on to stable output |
4.5 s |
| Programming |
PR 5909 Loop Link communications interface |
| Signal / noise ratio |
> 60 dB |
| EEprom error check |
< 3.5 s |
| Accuracy |
Better than 0.05% of selected range |
| Signal dynamics, input |
20 bit |
| Signal dynamics, output |
16 bit |
| Effect of supply voltage change |
< 0.005% of span / VDC |
| EMC immunity influence |
< ±0.5% of span |
| Extended EMC immunity: NAMUR NE21, A criterion, burst |
< ±1% of span |
Input specifications
| Max. offset |
50% of selected max. value |
| RTD type |
Pt100, Ni100, lin. R |
| Cable resistance per wire |
5 Ω (max.) |
| Sensor current |
Nom. 0.2 mA |
| Effect of sensor cable resistance (3-/4-wire) |
< 0.002 Ω / Ω |
| Sensor error detection |
Yes |
| Linear resistance min….max. |
0 Ω…5000 Ω |
Output specifications
| Updating time |
440 ms |
| Signal range |
4…20 mA |
| Min. signal range |
16 mA |
| Load (@ current output) |
≤ (Vsupply – 7.2) / 0.023 [Ω] |
| Load stability |
≤ 0.01% of span / 100 Ω |
| Sensor error indication |
Programmable 3.5…23 mA |
| NAMUR NE43 Upscale/Downscale |
23 mA / 3.5 mA |
| of span |
= of the presently selected range |