PR2914 Two-wire room temperature transmitter
Common input specifications |
|
| Max. offset | 50% of max.°C |
RTD input |
|
| Sensor current | > 0.2 mA, < 0.4 mA |
| Measurement range | 0…70°C |
| Min. measurement range | 25°C (span) |
Current output |
|
| Signal range | 4…20 mA |
| Min. signal range | 16 mA |
| Load (@ current output) | ≤ (Vsupply – 8) / 0.023 [Ω] |
| Load stability | ≤ 0.01% of span / 100 Ω |
| NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |