PR Electronics 2-wire transmitter with HART protocol PR 5335A

2026-03-24

PR5335A Two-wire transmitter with HART protocol

Input specifications

Common input specifications

Max. offset 50% of selected max. value

RTD input

RTD type Pt100, Ni100, lin. R
Cable resistance per wire 5 Ω (up to 50 Ω per wire is possible with reduced measurement accuracy)
Sensor current Nom. 0.2 mA
Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω
Sensor error detection Yes

TC input

Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5
Cold junction compensation (CJC) < ±1.0°C
Sensor error detection Yes
Sensor error current: When detecting / else Nom. 33 μA / 0 μA

Voltage input

Measurement range -800…+800 mV
Min. measurement range (span) 2.5 mV
Input resistance 10 MΩ

Output specifications

Current output

Signal range 4…20 mA
Min. signal range 16 mA
Load (@ current output) ≤ (Vsupply – 8) / 0.023 [Ω]
Load stability ≤ 0.01% of span / 100 Ω
Sensor error indication Programmable 3.5…23 mA
NAMUR NE43 Upscale/Downscale 23 mA / 3.5 mA
of span = of the presently selected range