PR3117 Bipolar isolated converter
Current input |
|
| Measurement range | -23…+23 mA |
| Programmable measurement ranges | ± 10 and ± 20 mA |
| Input voltage drop | < 1 VDC @ 23 mA |
Voltage input |
|
| Measurement range | -11.5…+11.5 V |
| Programmable ranges | ±5 and ±10 V |
| Input resistance | ≥ 1 MΩ |
Current output |
|
| Signal range | 0…23 mA |
| Programmable signal ranges | 0 / 4…20 mA |
| Load (@ current output) | ≤ 600 Ω |
| Load stability | ≤ 0.002% of span / 100 Ω |
| Current limit | ≤ 28 mA |
Voltage output |
|
| Signal range | 0…10 VDC |
| Programmable signal ranges | 0/1…5 and 0/2…10 V |
| Load (@ voltage output) | ≥ 10 kΩ |
| of span | = of the presently selected range |