| Signal range |
3.5…23 mA |
| Load (@ current output) |
≤ 600 Ω |
| Load stability |
≤ 0.01% of span / 100 Ω |
| Current limit |
≤ 28 mA |
| Effect of external 2-wire supply voltage variation |
< 0.005% of span / V |
| Max. external 2-wire supply |
26 VDC |
| Relay function |
N.C. |
| Programmable low setpoint |
0…29.9 mA |
| Programmable high setpoint |
0…29.9 mA |
| Hysteresis for setpoints |
0.1 mA |
| Max. voltage |
125 VAC / 110 VDC |
| Max. current |
0.5 AAC / 0.3 ADC |
| Max. voltage – hazardous installation |
32 VDC / 32 VAC |
| Max. current – hazardous installation |
1 ADC / 0.5 AAC |
| of span |
= normal measurement range 4…20 mA |