PR9106B HART transparent repeater
Current input |
|
| Measurement range | 3.5…23 mA |
| 2-wire transmitter supply 9106B1x (Uo = 27.5 VDC) | >16 V / 20 mA |
| 2-wire transmitter supply 9106B2x (Uo = 25.3 VDC) | >15 V / 20 mA |
| Sensor error detection: Loop break 4…20 mA | < 1 mA |
| Input voltage drop, supplied unit | < 4 V @ 23 mA |
| Input voltage drop, non-supplied unit | < 6 V @ 23 mA |
Current output |
|
| Signal range | 3.5…23 mA |
| Load (@ current output) | ≤ 600 Ω |
| Load stability | ≤ 0.01% of span / 100 Ω |
| Current limit | ≤ 28 mA |
Passive 2-wire mA output |
|
| Effect of external 2-wire supply voltage variation | < 0.005% of span / V |
| Max. external 2-wire supply | 26 VDC |