PR Electronics Isolated universal converter PR 3114

2026-04-17

PR3114 Isolated universal converter

Input specifications

RTD input

RTD type Pt10/20/50/100/200/250; Pt300/Pt400/500/1000; Ni50/100/120/1000
Cable resistance per wire 50 Ω (max.)
Sensor current Nom. 0.2 mA
Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω
Sensor error detection Yes
Short circuit detection < 15 Ω

Linear resistance input

Linear resistance min….max. 0 Ω…10000 Ω

Potentiometer input

Potentiometer min….max. 10 Ω…100 kΩ

TC input

Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
CJC via int. mounted sensor ±(2.0°C + 0.4°C * Δt)
Sensor error detection Yes
Sensor error current: When detecting / else Nom. 2 μA / 0 μA

Current input

Measurement range 0…23 mA
Programmable measurement ranges 0…20 and 4…20 mA
Input resistance Nom. 20 Ω + PTC 50 Ω

Voltage input

Measurement range 0…12 VDC
Programmable measurement ranges 0/0.2…1, 0/1…5, 0/2…10 VDC
Input resistance Nom. 10 MΩ
2-wire transmitter supply > 15 V / 20 mA

Output specifications

Current output

Signal range 0…23 mA
Programmable signal ranges 0…20/4…20/20…0/20…4 mA
Load (@ current output) ≤ 600 Ω
Load stability ≤ 0.01% of span / 100 Ω
Sensor error indication 0 / 3.5 / 23 mA / none
NAMUR NE43 Upscale/Downscale 23 mA / 3.5 mA
Current limit ≤ 28 mA

Voltage output

Signal range 0…10 VDC
Programmable signal ranges 0/0.2…1; 0/1…5 ; 0/2…10; 1…0.2/0; 5…1/0; 10…2/0 V
Load (@ voltage output) ≥ 10 kΩ
of span = of the presently selected range

国内销售
International sales