PR Electronics Temperature / mA converter, EMPHASIS assessed PR 9113B-EMP

2026-04-06

PR9113B-EMP Temperature / mA converter, EMPHASIS assessed

Input specifications

RTD input

RTD type Pt10/20/50/100/200/250; Pt300/Pt400/500/1000; Ni50/100/120/1000
Cable resistance per wire 50 Ω (max.)
Sensor current Nom. 0.2 mA
Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω
Sensor error detection Programmable ON / OFF

TC input

Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC) via ext. sensor in 5910 20…28°C ≤ ±1°C, -20…20°C / 28…70°C ≤ 2°C
CJC via int. mounted sensor ±(2.0°C + 0.4°C * Δt)
Sensor error detection Programmable ON or OFF (only wire breakage)
Sensor error current: When detecting / else Nom. 2 μA / 0 μA

Current input

Measurement range 0…23 mA
Programmable measurement ranges 0…20 and 4…20 mA
Input resistance Nom. 20 Ω + PTC 50 Ω
Sensor error detection Programmable ON / OFF

Output specifications

Current output

Signal range 0…23 mA
Programmable signal ranges 0…20/4…20/20…0/20…4 mA
Load (@ current output) ≤ 600 Ω
Load stability ≤ 0.01% of span / 100 Ω
Sensor error indication 0 / 3.5 / 23 mA / none
NAMUR NE43 Upscale/Downscale 23 mA / 3.5 mA
Output limitation, on 4…20 and 20…4 mA signals 3.8…20.5 mA
Output limitation, on 0…20 and 20…0 mA signals 0…20.5 mA
Current limit ≤ 28 mA

Passive 2-wire mA output

Max. external 2-wire supply 26 VDC
Effect of external 2-wire supply voltage variation < 0.005% of span / V