PR4179 Universal AC / DC transmitter
Current input |
|
| Signal range | 0…5 AAC / 40…400 Hz |
| Maximum input limit | 6.00 AAC @ 40°C |
| Programmable measurement ranges | 0…0.5; 0…1; 0…2.5 & 0…5 AAC |
| Custom configurable signal range | 0…5 AAC /40…400 Hz |
| Min. measurement range (span) | 0.5 AAC |
| Input resistance | < 0.042 Ω (incl. terminals) |
Voltage input |
|
| Signal range | 0…300 VAC / 40…400 Hz |
| Programmable measurement ranges | 0…0.5, 0…1, 0…2.83, 0…5, 0…120, 0…230 & 0…300 VAC |
| Custom configurable signal range | 0…300 VAC / 40…400 Hz |
| Min. measurement range (span) | 0.5 VAC |
| Input resistance | Nom. 3 MΩ || 100 pF |
Active unipolar and bipolar mA output |
|
| Programmable ranges | 0…20, 4…20 and S4…20 mA ±10 and ±20 mA Direct or Inverted Action |
| Load (@ current output) | ≤ 800 Ω |
| V-curve function, active signals, 100-0-100% | 20-0-20 mA |
Passive 2-wire mA output |
|
| Programmable ranges | 0…20 and 4…20 mA Direct or Inverted action |
| V-curve function, 100-0-100% | 20-0-20 mA |
| External loop supply | 3.5…30 V |